JC-217 Transmisor de temperatura con visualización in situ

The JC-217 on-site display temperature transmitter is used for the input of resistance temperature detector (RTD) signal and thermocouple (TC) signal and two-wire analog signal output (4−20mA).

  • Duración del precio: FOB/CIF/EXW/DAP
  • Paquete: Exportado Caja de madera o de acuerdo a la petición del cliente
  • Plazo de entrega7 a 10 días laborables
  • Transportes: Por mar, por aire, por expreso
  • Puerto de embarque: Puerto de Shanghai
  • Origen del lugar: Jiangsu
  • Garantía: 12 meses

Parámetros técnicos

 

Entrada
Input Signal RTD and TC
Scope of Cold Junction Compensation Temperature -20−70℃
Compensation Accuracy ±1℃
Salida
Output Signal 4−20mA (The input and output are not isolated.)
Load Resistance RL ≤ (Ue-12)/0.021
Output Current for Upper/Lower Limit Overflow Alarm IH=21mA、IL=3.8mA

IH=21mA and IL=3.8mA

Output Current for Input Break Alarm 21mA
Fuente de alimentación
Power Supply Voltage DC12−40V
Other Parameters
Thermal Drift 0.01%FS/℃
Tiempo de respuesta 700ms, reaches 90% of the final value.
Environment Temperature -20−70℃
Clase de protección IP65, anti-dust and anti-spray
Conexión M27×2 internal thread
EMC Comply with the industry equipment application requirements in GB/T18268 (IEC 61326-1).

Input Type and Transmission Accuracy:

Modelo Symbol Signal Type Measurement Range Minimum Measurement Range Range Scope Transfer Accuracy
Resistance Temperature Detector (RTD) Pt100 Pt100 -199.9−850.0℃ 10℃ ≤100℃ 0.2%
>100℃ 0.1%
Cu50 -50.0−150.0℃ 10℃ ≤100℃ 0.2%
>100℃ 0.1%
Thermocouple (TC) B 400−1800℃ 500℃ ≤300℃ 0.2%
>300℃ 0.1%
E -100−1000℃ 50℃ ≤300℃ 0.2%
>300℃ 0.1%
J -100−1200℃ 50℃ ≤300℃ 0.2%
>300℃ 0.1%
K -180−1372℃ 50℃ ≤300℃ 0.2%
>300℃ 0.1%
N -180−1300℃ 50℃ ≤500℃ 0.2%
>500℃ 0.1%
R -50−1768℃ 500℃ ≤500℃ 0.2%
>500℃ 0.1%
S -50−1768℃ 500℃ ≤500℃ 0.2%
>500℃ 0.1%
T -200−400℃ 50℃ ≤500℃ 0.2%
>500℃ 0.1%
Wre3-25

(Reserved)

0−2315℃ 500℃ ≤500℃ 0.2%
>500℃ 0.1%
Wre5-26

(Reserved)

0−2310℃ 500℃ ≤500℃ 0.2%
>500℃ 0.1%

NOTE:
1. Environment temperature for measuring the above accuracy is 20℃±2℃.
2. The output accuracy “%” is the allowance of the set range scope.
3. When measuring the TC, the allowance of cold junction compensation should be considered. The internal allowance of cold junction compensation is smaller than or equal to ±1℃.

 

 

 

 

 

Button Descriptions:

Set button (M) Used for switching among menu parameters. After modifying and saving the menu, press and hold the button back to the measurement value screen.
Decrease button (S) Used for decreasing or modifying the current flickering position. Press and hold the button to move the modification position to the right.
Increase button (Z) Used for increasing or modifying the current flickering position. Press and hold the button to move the modification position to the left.

 

 

In the work status, press and hold the Set button for 5 seconds to display the unlock symbol (LOC); Make LOC=1 and press the Set button to enter the menu. Press the Set button to change parameters and then press the Increase or Decrease button to modify parameter values.

Symbol Parámetro Range Scope Descripción Factory Default
Loc 0−50000 Electronic lock 0
Sn Refer to the input type list. Sensor type Pt100
Unidad ℃, F, R, K Temperature unit

℃: Celsius temperature

F: Fahrenheit temperature

R: Rankine temperature

K: thermodynamic temperature

℃
Filt 0−4 Damping coefficient 0
oPL -199.9−6300.0 Lower range limit -199.9
oPH -199.9−6300.0 Upper range limit 6300.0
PB -199.9−200.0 Measurement value transfer (zero-point) 0
PK 0.0000−1.9999 Measurement value transfer (gain) 1.0000
T-PB -199.9−200.0 Modification of cold junction temperature 0
Fout 3.800−21.000 Fault output current 21.000
diR 0−1 Current output direction

diR=0: output 4−20mA

diR=1: output 20−4mA

0
FiX 0.000−21.000 Constant current output: if the set value range is less than 3.800−21.000, the output is fixed based on the set value and is independent of the measurement. 0.000

Structure Diagram

Wiring Diagram

Instrument Model

Obtenga nuestro mejor presupuesto




    Scroll al inicio