JC0202 Explosion-proof Pressure Controller

The controller adopts bellows type sensor, which can be used for air, gas, water vapor and other neutral gases and water, refrigerant, oil, etc.

  • Price Term: FOB/CIF/EXW/DAP
  • Package: Exported Wooden case or according to customer request
  • Delivery Time:  7 to 10 working days
  • Transports: By sea, by air, by high express
  • Shipment Port: Shanghai Port
  • Origin of Place: Jiangsu
  • Warranty: 12 Months

 It can be used for vacuum. The setting value of the controller can be adjusted from -0.1 to 2.5MPa.

 The range of adjustment can be designed separately from -0.1 to 6.3MPa if there is special requirement.

Normal  Type Explosion-proof
Operating Viscosity

 

<1× 10-3m2/s <1× 10-3m2/s
Switching Element Micro switch Sealed Switches
 

Explosion Protection Class

Exde Ⅱ CT4~T6 Certificate of Conformity No.: GYB19.1360X
 

Enclosure Protection Level

 

IP65(Conforms to DIN40050, equivalent to  IP65 in GB4208) IP54 (Conforms to DIN40050, equivalent to  IP54 in  GB4208)
Ambient Temperature -40℃~50℃ -40℃~50℃
Medium Temperature 0~120℃ 0~120℃
Installation Position Pressure connection vertically down
Anti-Vibration Performance TL0202:40m/s2 ;TL0203:20m/s Max: 20m/s2
Repeatability Error ≤1% ≤1%
 

Contact Capacity

AC  220V  6A (Resistance) DC 250V  0.25A(Resistance)  60Wmax

AC 250V  5A(Resistance)  1250VAmax

JC0202 Switching Difference Is Not Adjustable 

Set Value

Adjustment

Range Mpa

Switching

Difference Is Not Greater Than  Mpa

Maximum Allowable Pressure

Mpa

Switching

 Times

Times/Min

 

Pressure Sensor Materials Interface Female Thread    W

Kg

 Dimension Drawing
Housing Bellows Normal Ex-Proof
-0.1~0 0.007 1 20 Brass Stainless Steel

00Cr17

Ni14

Mo2

(316L)

G1/4″ 1.0 01 04
-0.1~0.1 0.008
-0.1~0.16 0.009
-0.1~0.25 0.012
0~0.1 0.008
0~0.16 0.009
0.01~0.25 0.01
0.02~0.4 0.03 2 0.85 02 05
0.03~0.6 0.035
0.03~1 0.04
0.05~1.6 0.08 5 0.9 03 06
0.05~2.5 0.09

 

JC0202 Switching Difference Is Adjustable

Set Value

Adjustment

Ranga Mpa

Difference Is Not Greater Than  Mpa Maximum Allowable Pressure

Mpa

Switching

Times

Times/Min

 

Pressure Sensor Materials Interface Female Thread    W

Kg

Dimension Drawing
Housing Bellows Normal Ex-Proof
-0.1~0 0.019 1 20 Brass Stainless Steel

00Cr17

Ni14

Mo2

(316L)

G1/4″ 1.05 01 04
-0.1~0.1 0.021
-0.1~0.16 0.022
-0.1~0.25 0.024
0~0.1 0.016
0~0.16 0.02
0.01~0.25 0.024
0.02~0.4 0.08 2 0.9 02 05
0.03~0.6 0.09
0.03~1 0.1
0.05~1.6 0.19 5 0.95 03 06
0.05~2.5 0.2

 

JC0203 Switching Difference Is Not Adjustable (Small Switching Difference,No Explosion-Proof Type)

Set Value

Adjustment

Range  Mpa

Switching

Difference Is Not Greater Than  Mpa

Maximum Allowable Pressure

Mpa

Switching Times

Times/Min

 

Pressure Sensor Materials Interface Female Thread    W

Kg

Dimension Drawing
Housing Bellows
-0.1~0 0.0045 1 20 Brass Stainless Steel

00Cr17

Ni14

Mo2

(316L)

G1/4″ 1.0 01
-0.1~0.1 0.005
-0.1~0.16 0.0065
-0.1~0.25 0.01
0~0.1 0.0045
0~0.16 0.006
0.01~0.25 0.007
0.02~0.4 0.016 2 0.85 02
0.03~0.6 0.02
0.03~1 0.03
0.05~1.6 0.05 5 0.9 03
0.05~2.5 0.06

Note: ① In actual operation, even brief pressure peaks should not exceed this value.

Instructions For Selection And Installation Of Controller

See selection and installation of controller for details

Adjustment Of The Set Value

For details, see the adjustment of the set value of the pressure controller Example I, Example II, Example V

Normal  Type

01

Pressure Controller

02

Pressure Controller

03

Pressure Controller

Ex-proof  Type

04

Explosion-proof Pressure Controller

05

Explosion-proof Pressure Controller

06

Explosion-proof Pressure Controller

Electrical Wiring Diagram

The process of single knife double-throw micro switch action.

Wiring terminal 1-3 pressure rise to the upper switching value is switched on;

Wiring terminal 1-2 pressure rise to the upper switching value disconnect

Get Our Best Quotation




    Scroll to Top