JC1217 Pressure Controller
■ The controller adopts spring tube type sensor, the controller can be used for corrosive gas and liquid medium, and the setting value of the controller is adjustable, and the adjustment range is 1 ~ 40MPa.
■ The controller has a large pressure control range, high control accuracy, small switching difference.
■ The sensor of the controller is suitable for corrosive media (gas or liquid).
- Price Term: FOB/CIF/EXW/DAP
- Package: Exported Wooden case or according to customer request
- Delivery Time: 7 to 10 working days
- Transports: By sea, by air, by high express
- Shipment Port: Shanghai Port
- Origin of Place: Jiangsu
- Warranty: 12 Months
- Main Technical Performance
- Specification
- Adjustment Of The Set Value
- Instructions For Selection And Installation Of Controller
- External Dimensions And Mounting Dimensions (Unit: mm)
- Electrical Wiring Diagram
Working Viscosity | ≤400 mm2/s |
Switching Element | Micro switch (Group 1) |
Enclosure Protection Level | IP65 |
Ambient Temperature | -25℃~55℃ |
Medium Temperature | 0℃~88℃ |
Installation Position | At will |
Anti-Vibration Performance | Max 10 m/s2 |
Repeatability Error | ≤ 1% |
Contact Capacity | V max=380VAC I max=6A (resistive) P max=600VA |
Switching Difference Is Not Adjustable
Set Value
Adjustment Range Mpa |
Switching
Difference Is Not Greater Than Mpa |
Maximum Allowable Pressure
①Mpa |
Switching
Times Times/Min |
Pressure Sensor Materials | Interface Male Thread | Dimensions Drawing Number |
1~10 | 0.20 | 15 | 60 | 316L | G1/2″ | 01 |
1~16 | 0.32 | 20 | ||||
2~25 | 0.50 | 32 | ||||
2~40 | 0.80 | 50 |
Note: ① In actual operation, even brief pressure peaks should not exceed this value.
[Example]: The controller with a set value adjustment range of 2~40MPa is selected, and the pressure is required to rise to 26MPa (upper switching value) to issue a contact signal, and the operation steps are as follows:
- Screw the product onto the threaded interface of the pressure calibration table, noting that the flat part of the sensor must be clamped with a wrench to prevent the relative rotation of the switch housing and the sensor;
- Open the cover and connect the cable through the cable connector to the terminal block, and the other end of the cable to a multimeter or indicator;
- Increase the pressure to 26MPa, a value that can be read from a standard manometer, and then turn the upper adjustment screw counterclockwise so that the set value changes from small to large until the switch contact switches at 26MPa;
- Loosen the locking device and turn the set value adjusting screw counterclockwise so that the set value changes from small to large until the switch contact switches at 26MPa;
- Tighten the locking device, adjust the pressure of the pressure calibration table, so that the pressure changes back and forth in 26MPa, and check whether the switch value of the contract is 26MPa when the pressure rises, this value is to set the upper switching value, the corresponding lower switching value should be 26MPa minus the switching value of 0.8MPa (or so), that is, 25.2MPa (or so).
- Selection of the controller, the best to make the scheduled set value is located in the middle of the controller set value adjustment range, generally for the adjustment 20% to 80% of the range;
- If the controller is to be installed outdoors, sufficient protection should be given to avoid the effects of drastic changes in ambient temperature, direct sunlight, corrosive gases or water infiltration, etc;
- When installing the cable, the compression nut at the cable introduction should be tightened to avoid the loosening of the cable and to effectively prevent the infiltration of water and other liquids, etc.
4 . The on/off current cannot be greater than the contact capacity.
5 . Pay special attention when mounting (or dismounting) the controller: the flat part of the sensor must be held with a wrench to prevent the sensor’s relative rotation and switch housing.
The process of single knife double-throw microswitch action.
Wiring terminal 1-3 pressure rise to the upper switching value is switched on;
Wiring terminal 1-2 pressure rise to the upper switching value disconnect.