JCTT-211 Integrated Temperature Transmitter

JCTT-211 integrated temperature transmitter utilizes the characteristic of the platinum resistance, which changes its resistance value with temperature variations in a specific functional relationship, to measure the temperature of the measured medium.

JCTT-211 integrated temperature transmitter is a compact temperature sensor with a built-in temperature conversion module. It consists of three parts: temperature sensor, compensation circuit, and conversion circuit. It employs integrated packaging technology to combine temperature conversion and components into a single unit, and is particularly suitable for situations with limited space, high measurement accuracy requirements, and vibrating environments.

details-temperature transmitter

JCTT-211 integrated temperature transmitter features

  • a compact size
  • easy installation
  • stable performance
  • high sensitivity
  • strong reliability
  • accurate temperature measurement

feature-temperature transmitter

JCTT-211 integrated temperature transmitter is widely applied in automated temperature measurement and control systems for industries such as pharmaceuticals, plastics, food, packaging, metallurgy, machinery, textiles, and more.

temperature transmitter conversion board

The temperature transmitter adopts a fully welded structure with a high-strength stainless steel housing.

temperature transmitter housing

Input
Input Signal Pt100 or Pt1000(Platinum Resistance)
Range -50~450℃
Accuracy Grade 0.3、0.5 class optional
Output
Output Signal 4~20mA、0~10V
Power Supply
Supply Voltage 12~40VDC
Other Parameters
Insulation Strength 100MΩ( at the 250VDC)
Long-Term Stability ≤0.2%FS/Year
Temperature Drift ±0.2%FS/℃
Response Time ≤30s
Insertion Diameter d (special requirements negotiable)
Material Default 304 (customization available for special requirements)
Housing Protection IP65
Electrical Connection Hirschmann conncetor (electrical interface: internal thread M16*1.5)
Operating Temperature ambient temperature: -40~85℃, relative humidity: 0~95%RH
mechanical vibration: f≤55Hz, amplitude<0.15mm, power consumption: <0.5W

selection-temperature transmitter

①Process Connection ②Protective Tube Diameter ③Insertion Depth ④On-site Display Type
Code  Thread Specifications Code Insertion Diameter Code Insertion Depth(mm) Code On-site Display Type
C1

C2

C3

External thread M20*1.5

External thread M16*1.5

External thread M27*2

4

6

8

10

12

φ4

φ6

φ8

φ10

φ12

L 50、100、150、

200、300、450、

500、800、1000

A

B

No display

LED digital display

⑤Range ⑥Heat Sink Remark
Code Range Code Heat sink Default output is 4-20mA, and the voltage output can be customized.
Pt100 -50~450℃

Note: Optional according to user requirements; a heat sink is required when the range exceeds 150°C.

X

T

No heat sink

High-temperature type heat sink.

instrument wiringwiring method

Other Related Products