JCTXTC3 Smart Temperature Switch

■ The temperature sensing element of the JCTXTC3 intelligent temperature switch is different from the mechanical thermal expansion and contraction principle, but uses a high precision platinum RTD as the temperature sensor, when the medium temperature changes, its resistance value changes with the characteristics to detect the temperature. The integration of high-precision industrial circuit components, with high stability, non-contact type of intelligent temperature switch.

Fields Of Application

Monitoring of oil circuit temperatures    Cement industry

Electromechanical automation          Metallurgical industry

Lubrication systems                  Environmental industry

  • Price Term: FOB/CIF/EXW/DAP
  • Package: Exported Wooden case or according to customer request
  • Delivery Time:  7 to 10 working days
  • Transports: By sea, by air, by high express
  • Shipment Port: Shanghai Port
  • Origin of Place: Jiangsu
  • Warranty: 12 Months
Basic Parameters
Power Supply DC24V±5% or AC220V±5%
Measurement Range -50~300℃(optional)
Settable Range 20%FS-80%FS(best)
Display 4 Digital LCD
Accuracy 1%FS
Repeatability Error ≤0.5%FSmax
Temperature Drift ≤0.1%FSmax
Enclosure Protection Class IP65
Output 4-20mA Load ≤ 600 ohms Accuracy 0.5%FS
Output Method
Type PNP transistor output, SPST switching output
Action Life >1 million times
Response Time Action time:15ms Release time:8ms
Process Connection Stainless steel 304# M20×1.5(Regular)
Length Of Insertion Depth And Tube Diameter Stainless steel 304# Insert depth 100 Tube diameter Φ8 (Regular)
Environmental Conditions
Media Temperature -50-300℃
Ambient Temperature -25-80℃
JCTXTC3 – X XX XX . XX X X . XX                                                53      A B  C    D  E F   G
Note: Special Requirements To Be Specified At The Time Of Contracting
A: Power Supply
Code Power Supply
1 DC24V
2 AC220V
B: Sensor type
Code Sensor Type
PT PT100 Platinum RTD
C: Measurement Range
Code Measurement Range Code Measurement Range Code Measurement Range
A1 0-100℃ A2 0-150℃ A3 0-200℃
A4 0-250℃ A5 0-300℃ A6 0-160℃
A7 -10-100℃ A8 -50-100℃ A9 -50-250℃
B1 -40-80℃ B2 -40-200℃ B3 0-50℃
B4 -10-200℃ B5 -20-240℃ B6 -40-120℃
D: Logic Output
Code Logic Output
10 One way PNP (DC24V, 3A max)
11 Two way PNP (DC24V, 3A max)
12 Three way PNP (DC24V, 3A max)
30 One way relay (DC24V/AC250V, 3A max)
31 Two way relay (DC24V/AC250V, 3A max)
F:Analogue Output
Code Analogue Output
N /
B 4-20MA
G:Process Connection
Code Process Connection
54 M27*2 External insertion depth 100, diameter Φ10 (stainless steel 304#)
62 M27*2 External insertion depth 200, diameter Φ10 (stainless steel 304#)
66 M27*2 External insertion depth 100, diameter Φ8(stainless steel 304#)
79 M20*1.5 External insertion depth 100, diameter Φ8(stainless steel 304#)
82 G1/2″ External insert depth 100, diameter Φ8 (stainless steel 304#)
88 NPT1/2 External insertion depth 150, diameter Φ8 (stainless steel 304#)

Note: If with analogue output, up to one logic output is optional.

Smart Temperature Switch

Smart Temperature Switch.

Note: The supply voltage is determined by the selection, please do not randomly wired; the number of output channels is determined by the selection, no extra channels do not need to be wired.

  1. Key Description
    Project Function Description Operating Procedures
    Basic Settings Access to basic settings Press “Set” for 3 seconds to display “ST1”, press “â–²” to cycle through the panel: “ST1” “ST2” “ST3” “Ec”.
    St1

    (First Circuit Set Point)

    Start when temperature rises and temperature ≥ ST1 value

    the state switching starts (i.e.: normally open →normally closed, normally closed → normally open or DC24V ®→DC0V)

    When “ST1” is displayed, press the “Enter” key to enter the setting state of the first loop setting value, the blinking bit is modifiable at this time, press the “â–²” key, the blinking bit can be modified from 0 to 9 in a cycle, press the:”â–¶” key, the blinking bit can be moved in a cycle from thousands to single digits.  Press the “â–²” and “â–¶ ” keys to complete the setting of the set value, press the “Enter” key to store the set value and jump to display “ON ” or “OFF”.
    ON/OFF (First Circuit Start State) When “ON” is displayed, the circuit is switched on

    When the temperature rises and the temperature < ST1 value, the output

    is normally closed or DC24V;

    When “OFF” is displayed, the circuit is normally closed or DC24V when the temperature rises and the temperature is <ST1.

     

    Press the “â–²” key to switch back and forth between “ON” and “OFF”; press the “Enter” key to store the status value and jump to display “OL”.
    OL (First Circuit Delay Value) Temperature drops and temperature ≤ (ST1-OL)

    value, the output state is reset.

    When “OL” is displayed, press the “Enter” key to enter the setting state of the first circuit set value, the blinking bit is modifiable at this time, Press the “â–²” key, the blinking digit can be cyclically modified from 0 to 9, press the “â–¶ ” key, the blinking digit can be cyclically moved from thousands to individual digits. Press the “â–²” and “â–¶ ” keys to complete the setting of the set value, press the “Enter” key to store the delay value and jump to the display of “ST1. “
    The St2 Circuit Is Set As Above For The St1 Circuit And Will Not Be Described Further.
    Exit Exit basic settings When “Ec” is displayed, press the “Enter” key to exit the basic settings.
  2. Set Flow ChartSmart Temperature Switch1Note: Depending on the model and the number of output circuits, some circuit settings are not valid.

    â‘ Setting value: Pressure value at which the switch operates.

    â‘¡Start output state: oN for display pressure below set value switch action; oFF for display pressure above set value switch action.

    â‘¢Delay value: delay value = set value – reset value, i.e. switching difference.

  3. Fine Adjustment Of Current ValuesSmart Temperature Switch2Press and hold the “ENTER” and “â–²” keys simultaneously for 5 seconds, the DA value corresponding to 4mA will be displayed roughly, press the â–¶” key to adjust down, “â–²” key to adjust up, press the “ENTER” key to enter 20mA fine adjustment, press the “▶ ” key to adjust down, “â–²” key to adjust up. After adjustment,Press “ENTER” key to exit, that is to complete the current fine-tuning. (Note: The factory has been adjusted, no need to fine-tune under normal conditions.)

Smart Temperature Switch4

â‘ Wiring with electricity is strictly forbidden.

â‘¡Opening the panel is strictly forbidden.

â‘¢Good grounding.

â‘£Wiring should be done according to the instructions.