JC213 Head Temperature Transmitter Without Hart
JC213 Head Temperature Transmitter without hart is used for the signal input of resistance temperature detector (RTD) and thermocouple (TC) and 4 – 20mA analog output of the two-wire system.
- Introduction
- Parameters
- Wiring
- Video
JC213 Head Temperature Transmitter without hartÂ
JC213Head Temperature Transmitter is used for the signal input of resistance temperature detector (RTD) and thermocouple (TC) and 4 – 20mA analog output of the two-wire system, and can be installed in the sensor(Form B) through the HART protocol configuration.
DimensionÂ
Tags:Â Head Temperature Transmitter without hartthermocouple temperature transmitter with hart4-20ma temperature transmitterHead Temperature Transmittertemperature transmitter with PT100 sensortemperature sensor transmittersmart temperature transmitterhead temperature transmitter with pt100temperature transmitter with 4-20ma output
Technical Parameter for JC213 Head Temperature Transmitter without hartÂ
Input | |
Input signal | Resistance temperature detector (RTD) and thermocouple (TC) |
Cold-junction compensation temperature scope | -20 -60℃ |
Compensation precision | ±1℃ |
Output | |
Output signal | 4-20mA, overlaid HART protocol |
Load resistance | RL≤(Ue-12)/0.021 |
Output current of upper and lower limit overflow alarm | IH=21mA, IL=3.8mA |
Output current of input disconnection alarm | Settable |
Power supply | |
Supply voltage | DC12-40V |
Other parameters | |
Transmission precision (20℃) | 0.1%FS |
Temperature drift | 0.0075%FS/℃ |
Response time | Reach to 90% of the final value for700ms |
Used environmental temperature | -40 – 80℃ |
Storage temperature | -40 – 100℃ |
Insulation strength (between input and output) | 1500Vrms (1 min, without spark) |
Insulation resistance (between input and output) | ≥100MΩ(under the 500 VDC) |
Condensation | Allowable |
Protection level | IP00; IP66 (installation) |
Aseismicity | 4g/2Â –Â 150Hz |
Installation angle | Unlimited |
Installation area | B-type top cassette installation |
Electromagnetic compatibility | Conform to GB/T18268 industrial equipment application requirements (IEC 61326-1) |
Input Type Table:Â
Model | Type | Measurement scope | Minimum measurement scope |
Resistance temperature detector
(RTD) |
Pt100 | -200.0~850.0℃ | 20℃ |
Cu50 | -50.0~150.0℃ | 20℃ | |
Thermocouple (TC) |
B | 400~1820℃ | 500℃ |
E | -100~1000℃ | 50℃ | |
J | -100~1200℃ | 50℃ | |
K | -180~1372℃ | 50℃ | |
N | -180~1300℃ | 50℃ | |
R | -50~1768℃ | 500℃ | |
S | -50~1768℃ | 500℃ | |
T | -200~400℃ | 50℃ |
Tags:Â Head Temperature Transmitter without hartthermocouple temperature transmitter with hart4-20ma temperature transmitterHead Temperature Transmittertemperature transmitter with PT100 sensortemperature sensor transmittersmart temperature transmitterhead temperature transmitter with pt100temperature transmitter with 4-20ma output
WiringÂ
Configuration Schematic Diagram
Tags:Â Head Temperature Transmitter without hartthermocouple temperature transmitter with hart4-20ma temperature transmitterHead Temperature Transmittertemperature transmitter with PT100 sensortemperature sensor transmittersmart temperature transmitterhead temperature transmitter with pt100temperature transmitter with 4-20ma output
JC213 Head Temperature Transmitter without hart
Tags:Â Head Temperature Transmitter without hartthermocouple temperature transmitter with hart4-20ma temperature transmitterHead Temperature Transmittertemperature transmitter with PT100 sensortemperature sensor transmittersmart temperature transmitterhead temperature transmitter with pt100temperature transmitter with 4-20ma output