EJCBS-Sanitary Gauge Pressure Transmitter

Sanitary Gauge Pressure Transmitter is used to measure the pressure of liquid or gas. It can also measure the sanitary level of a liquid and then convert .It to a 4-20 mADC HART current signal output. The EJCB-S can communicate with the 375 handheld terminal or the 100 Modem for parameter setting, process monitoring, and more.

Sanitary Gauge Pressure Transmitter  EJCBS

Sanitary Gauge Pressure Transmitter   is used to measure the pressure of liquid or gas. It can also measure
the sanitary level of a liquid and then convert .It to a 4-20 mADC HART current signal output. The EJCB-S can communicate with the 375 handheld terminal or the 100 Modem for parameter setting, process  monitoring, and more.

Standard Specifications

(Adjusting the range based on the standard zero point, stainless steel 316L diaphragm,

filling fluid is silicone oil)

1 Performance Specifications

Reference Accuracy of Span Adjusting

±0.1% (including nonlinearity,

hysteresis and repeatability)

If TD>10 (TD=maximum range/adjust range),

it is: RP1002-CS: ±(0.01×TD)%

Ambient Temperature Influence

 Total Influence when -25℃~65℃

±(0.15×TD+0.05)%×Span

Total Influence when -40℃~-25℃

And 65℃~85℃

±(0.2×TD+0.05)%×Span

Over range Influence

 ±0.075%×Span

Stability

±0.1%×Span /3 yearserf

Model(Gauge Pressure Transmitter
EJCBP
Output S Basic Accuracy 0.1%
Span
Gauge Pressure B 0-3kPa~6kPa /(0-300~600 mmH2O)
C 0-4kPa~40kPa /(0-400~4000 mmH2O)
D 0-10kPa~250kPa /(0-1~25 mH2O)
F 0-100kPa~3MPa /(0-10~300 mH2O)
Diaphragm fill fluid S 316L stainless steel Silicone oil
C Hastelloy C Silicone oil
R Titanium Alloy
Process connector Size 1 Tri-clamp 1” / DN 25(Capillary length select 0)
2 Tri-clamp 1.5” / DN 40
3 Tri-clamp 2” / DN 50
4 Tri-clamp 2.5” / DN 65
5 Tri-clamp 3” / DN 80
Capillary Length 0 None
1to 6 1 to 6 M
S  Special
Mounting Bracket N None
1 304 stainless steel
2 Carbon steel galvanized
Integral indicator N None
1 Backlit LCD display
Additional S SS housing

How to order  EJCBS Sanitary Gauge Pressure Transmitter

  1. 1.Range
  2. 2.Medium
  3. 3.Working pressure
  4. 4.Working temperature
  5. 5.Tri clamp Size
  6. 6.Working pressure
  7. 7.Other requirement

Scroll to Top