JC-217 Трансмиттер температуры с индикацией на месте
The JC-217 on-site display temperature transmitter is used for the input of resistance temperature detector (RTD) signal and thermocouple (TC) signal and two-wire analog signal output (4−20mA).
- Цена Срок: FOB/CIF/EXW/DAP
- Пакет: Экспортируется деревянный ящик или в соответствии с запросом клиента
- Время доставки: 7-10 рабочих дней
- Перевозки: По морю, по воздуху, экспрессом
- Порт отгрузки: Шанхайский порт
- Происхождение места: Цзянсу
- Гарантия: 12 месяцев
- Технические характеристики
- Operations
- Menu settings
- Structure diagram
- Wiring Diagram
- Instrument model
Технические параметры
| Вход | |
| Input Signal | RTD and TC |
| Scope of Cold Junction Compensation Temperature | -20−70℃ |
| Compensation Accuracy | ±1℃ |
| Выход | |
| Output Signal | 4−20mA (The input and output are not isolated.) |
| Load Resistance | RL ≤ (Ue-12)/0.021 |
| Output Current for Upper/Lower Limit Overflow Alarm | IH=21mA、IL=3.8mA
IH=21mA and IL=3.8mA |
| Output Current for Input Break Alarm | 21mA |
| Источник питания | |
| Power Supply Voltage | DC12−40V |
| Other Parameters | |
| Thermal Drift | 0.01%FS/℃ |
| Время отклика | 700ms, reaches 90% of the final value. |
| Environment Temperature | -20−70℃ |
| Класс защиты | IP65, anti-dust and anti-spray |
| Соединение | M27×2 internal thread |
| EMC | Comply with the industry equipment application requirements in GB/T18268 (IEC 61326-1). |
Input Type and Transmission Accuracy:
| Модель | Symbol | Signal Type | Диапазон измерений | Minimum Measurement Range | Range Scope | Transfer Accuracy |
| Resistance Temperature Detector (RTD) | Pt100 | Pt100 | -199.9−850.0℃ | 10℃ | ≤100℃ | 0.2% |
| >100℃ | 0.1% | |||||
| Cu50 | -50.0−150.0℃ | 10℃ | ≤100℃ | 0.2% | ||
| >100℃ | 0.1% | |||||
| Термопара (TC) | B | 400−1800℃ | 500℃ | ≤300℃ | 0.2% | |
| >300℃ | 0.1% | |||||
| E | -100−1000℃ | 50℃ | ≤300℃ | 0.2% | ||
| >300℃ | 0.1% | |||||
| J | -100−1200℃ | 50℃ | ≤300℃ | 0.2% | ||
| >300℃ | 0.1% | |||||
| K | -180−1372℃ | 50℃ | ≤300℃ | 0.2% | ||
| >300℃ | 0.1% | |||||
| N | -180−1300℃ | 50℃ | ≤500℃ | 0.2% | ||
| >500℃ | 0.1% | |||||
| R | -50−1768℃ | 500℃ | ≤500℃ | 0.2% | ||
| >500℃ | 0.1% | |||||
| S | -50−1768℃ | 500℃ | ≤500℃ | 0.2% | ||
| >500℃ | 0.1% | |||||
| T | -200−400℃ | 50℃ | ≤500℃ | 0.2% | ||
| >500℃ | 0.1% | |||||
| Wre3-25
(Reserved) |
0−2315℃ | 500℃ | ≤500℃ | 0.2% | ||
| >500℃ | 0.1% | |||||
| Wre5-26
(Reserved) |
0−2310℃ | 500℃ | ≤500℃ | 0.2% | ||
| >500℃ | 0.1% |
NOTE:
1. Environment temperature for measuring the above accuracy is 20℃±2℃.
2. The output accuracy “%” is the allowance of the set range scope.
3. When measuring the TC, the allowance of cold junction compensation should be considered. The internal allowance of cold junction compensation is smaller than or equal to ±1℃.
Button Descriptions:
| Set button (M) | Used for switching among menu parameters. After modifying and saving the menu, press and hold the button back to the measurement value screen. |
| Decrease button (S) | Used for decreasing or modifying the current flickering position. Press and hold the button to move the modification position to the right. |
| Increase button (Z) | Used for increasing or modifying the current flickering position. Press and hold the button to move the modification position to the left. |
In the work status, press and hold the Set button for 5 seconds to display the unlock symbol (LOC); Make LOC=1 and press the Set button to enter the menu. Press the Set button to change parameters and then press the Increase or Decrease button to modify parameter values.
| Symbol | Параметр | Range Scope | Описание | Factory Default |
| Loc | 0−50000 | Electronic lock | 0 | |
| Sn | Refer to the input type list. | Тип датчика | Pt100 | |
| Единица | ℃, F, R, K | Temperature unit
℃: Celsius temperature F: Fahrenheit temperature R: Rankine temperature K: thermodynamic temperature |
℃ | |
| Filt | 0−4 | Damping coefficient | 0 | |
| oPL | -199.9−6300.0 | Lower range limit | -199.9 | |
| oPH | -199.9−6300.0 | Upper range limit | 6300.0 | |
| PB | -199.9−200.0 | Measurement value transfer (zero-point) | 0 | |
| PK | 0.0000−1.9999 | Measurement value transfer (gain) | 1.0000 | |
| T-PB | -199.9−200.0 | Modification of cold junction temperature | 0 | |
| Fout | 3.800−21.000 | Fault output current | 21.000 | |
| diR | 0−1 | Current output direction
diR=0: output 4−20mA diR=1: output 20−4mA |
0 | |
| FiX | 0.000−21.000 | Constant current output: if the set value range is less than 3.800−21.000, the output is fixed based on the set value and is independent of the measurement. | 0.000 |





